SA2100,power quality analyzer,portable power analyzer by Xiamen Wellzion Electronics Co., Ltd
- Item Condition:
- Brand:
- Model#:
- Location:
- Price:
Product Description
Specifications
Safety: CAT III 1000V / CAT IV 600VSingle-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W
Support USB port and LAN port
Features and Benefits
Safety: CAT III 1000V / CAT IV 600V
Standards: IEC61000-4-30 (2008) S class, EN50160 (2007)
Easy operation to capture the power quality problem
Single-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W
Display: Run Chart, Bar Chart, Vector Graphic, Waveform, Event List, Readings.
8G Memory Card to make the long-term measuring data storage
Support USB port to connect to PC and analyze the data/screen shots copied by U-disk
Support LAN port to make the remote control available, transfer the measuring data
Specifications
| Specifications | Measurement Range | Resolution | Accuracy |
| Voltage/Current/Frequency | |||
| Channel | 3-phase line input + 1 neutral line input | ||
| Vrms(dc+ac) | 1 ~ 1000Vrms | 0.1Vrms | ±5% |
| Vpk | 1 ~ 1400Vpk | 0.1Vpk | ±5% |
| V(CF) | 1.0 ~ >2.8 | 0.01 | ±5% |
| Arms | 1~ 3000A | 1A | ±1% ± 5digits |
| 1~ 300A | 0.1A | ±1% ± 5digits | |
| Apk | 1 ~ 4000Apk | 1A | ±1% ± 5digits |
| A(CF) | 1 ~ 10 | 0.01 | ±5% |
| Frequency | 42.5~57.5Hz(50Hz nominal) | 0.01Hz | ±0.01% |
| 51~69Hz(60Hz nominal) | 0.01Hz | ±0.01% | |
| Dips & Swells | |||
| Vrms1/2 | 0 ~ 200% of nominal voltage | 0.1Vrms | ±1% |
| Arms1/2 | 1 ~ 3000A | 1A | ±1% ±5 counts |
| 1 ~ 300A | 0.1A | ±1% ±5 counts | |
| Threshold levels | Programmable thresholds in percent of nominal voltage | ||
| Event detection based upon ½ cycle rms voltages | |||
| Captures Dips, Swells Interruptions and Rapid Voltage Changes | |||
| Duration | hhh,mm,ss,mmm | 0.5 cycle | 1 cycle |
| Harmonic | |||
| Harmonic Order | 1 ~ 50 | ||
| Inter-Harmonic Order | 1 ~ 49 | ||
| Voltage | 0.0 ~ 100.0% | 0.10% | ±0.1% ± nx0.1% |
| Current | 0.0 ~ 100.0% | 0.10% | ±0.1% ± nx0.1% |
| THD | 0.0 ~ 100.0% | 0.10% | ±2.5% |
| DC Relative | 0.0 ~ 100.0% | 0.10% | ±2% |
| Frequency | 0 ~ 3500Hz | 1Hz | 1Hz |
| Phase | -360° ~ 0° | 1° | ± nx1.5° |
| Power And Energy | |||
| Active Power/Apparent Power/Reactive Power | 1.0 ~ 20.00MW | 0.1kW | ±1.5±10 counts |
| Energy | 0.00kWh ~ 200GWh | 10Wh | ±1.5±10 counts |
| Power Factor | 0 ~ 1 | 0.01 | ±0.03 |
| Flicker | |||
| Pst(1min),Pst,Plt,PF5 | 0.00 ~ 20.00 | 0.01 | ±5% |
| Unbalance | |||
| Voltage | 0.0 ~ 5.0% | 0.10% | ±0.5% |
| Current | 0.0 ~ 20.0% | 0.10% | ±1% |
| Voltage Phase Angle | -360° ~ 0° | 1° | ±2digits |
| Current Phase Angle | -360° ~ 0° | 1° | ±5digits |
| Voltage Transient | |||
| Vpk | ±6000Vpk | 1V | ±15% |
| Vrms | 10 ~ 1000Vrms | 1V | ±2.5% |
| Min. Tested Time | 50us | ||
| Sampling Rate | 20kS/s | ||
| Inrush Current | |||
| Arms(AC+DC) | 0~3000Arms | 0.1 | ±1% ± 5digits |
| Inrush Duration | 6s ~ 32min selectable | 10ms | ±20ms |
| Logger | |||
| Recording | Parameter, duration time and time interval can be set by user, which can be export on PC | ||
| Memory | 8G | ||
| Max. recording time | 1 year | ||
| System Monitor | |||
| Parameters | Vrms,Arms,Harmonic Volts,THD Volts,Plt,Vrms1/2,Arms1/2,Vneg,Hz,dips and swells, unbalance | ||
| Record Time | 2h ~ 7days | ||
| Record Event Number | >10000 | ||
| Limits | According EN50160 or customer definable | ||
| General Characteristics | |||
| Power | AC220V(1±10%), 50Hz(1±5%), ≤10VA | ||
| Interface | USB_HOST, LAN | ||
| Display | 5.6' TFT LCD, 320*240 | ||
| Battery | 7.4V, 4.4Ah, > 7 hours working time | ||
| Dimension & Weight | 262×173×66mm, 1.6kg | ||