Specifications
1)Diesel generator
2)Low fuel consumption
3)8 hours base tank
4)ISO & CE approval Perkins gen
THE SPECIFICATIONS OF THE ENGINE:
| GENSET - 50 Hz at 1500 RPM | ENGINE DETAILS | ALTERNATOR |
| | Open Type | | | | | | | | | | |
| Model | PRIME | STANDBY | Model | R/Power | Type | No. of | Arrange. | Cubic | Fuel | STAMFORD |
| | kVA | kW | kVA | kW | | kW | Nat/asp | Cyls. | of Cyls. | Capacity | Cons. | Made in China |
| HUAXIN | | | | | Made in China | | or Turbo | | Inline/Vee | ltrs | ltrs/h | Model |
| | | | | | | | | | | | | |
| HP25GF | 31.25 | 25 | 34.375 | 27.5 | 1004G | 42 | Nat/asp | 4 | In line | 3.99 | 6.4 | BCI 184 G |
| HP30GF | 37.5 | 30 | 41.25 | 33 | 1004G | 42 | Nat/asp | 4 | In line | 3.99 | 7.7 | BCI 184 H |
| HP34GF | 42.5 | 34 | 46.75 | 37.4 | 1004G | 42 | Nat/asp | 4 | In line | 3.99 | 8.7 | BCI 184J |
| HP40GF | 50 | 40 | 55 | 44 | 1004TG | 66 | Turbo | 4 | In line | 3.99 | 10.3 | UCI 224D |
| HP48GF | 60 | 48 | 66 | 52.8 | 1004TG | 66 | Turbo | 4 | In line | 3.99 | 12.3 | UCI 224E |
| HP58GF | 72.5 | 58 | 79.75 | 63.8 | 1004TG | 66 | Turbo | 4 | In line | 3.99 | 14.9 | UCI 224F |
| HP68GF | 85 | 68 | 93.5 | 74.8 | 1006TG1A | 84 | Turbo | 6 | In line | 5.99 | 17.2 | UCI 224G |
| HP80GF | 100 | 80 | 110 | 88 | 1006TG2A | 92 | Turbo | 6 | In line | 5.99 | 20.2 | UCI 274C |
| HP96GF | 120 | 96 | 132 | 105.6 | 1006TAG | 121 | Turbo | 6 | In line | 5.99 | 23.5 | UCI 274D |
1) The rated speed : 1500rpm, four strokes, inline. Fan and water tank cooling system, up to the ISO3046 standard
2) The rated output: from 16kW (20kVA) to 120kW (150kVA)
start eddiciency
THE SPECIFICATIONS OF THE ALTERNATOR:
The world first class alternator, up to the GB755, BS5000, VDE0530, IEC34-1, CSA22.2, AS2359 standard,brushless and self-excitation,it be can supply excitation in many cases:
STAMFORD/ MARATHON/ LEROY SOMER/ QIANGHUI
Standard pitch winding can be inhibit currents nterruption
Insulation Class: H Protection class: H
Frequency at stable state: ≤±1.0%
Telephones interference: THF < 2%, TIF < 50
THE SPECIFICATIONS OF THE GENERATING SET:
The basic specifications: 230 / 400V AC, 50Hz / 60Hz, 0.8Pf , three phase four wires
Character: base fuel tank for 8 hours
Use: can be used for the open type and the soundproof type , automatic type
Control system:
a) Automatic alarm system: the unit has the acousto-optics alarm
system and arrestor for any situation as the start defeat, the water
is over temperature, the oil pulls down, over speed, over load and
over current
b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers
Supply standard collocation:
a) Diesel engine with all accessories, 3 filter, electric systems
b) Alternator
c) Steel structure
d) Fan and water tank cooling system
e) Flange connector
f) 12 / 24V starting motor and charge engine
g) Air cleaner, fuel cleaner, oil cleaner
h) On-board control panel
i) MCCB air conservation switch
j) 12 / 24V starting accumulator and Battery line
k) Set shock absorber